CPSC, Central Sprinkler Company Announce Voluntary Recall To Replace O-Ring Fire Sprinklers
What was recalled
This replacement program includes two kinds of sprinklers, "wet" and "dry." "Wet" sprinklers are installed in piping that is filled with water. "Dry" sprinklers are used in areas that may be exposed to very cold temperatures and the exposed piping does not contain water. Central manufactured 33 million "wet" sprinklers with O-rings from 1989 until 2000 that are covered by this program. Central also manufactured 2 million "dry" sprinklers with O-rings from the mid-1970's to June 2001 that are covered by this program. The program also covers 167,000 sprinklers with O-rings manufactured by Gem Sprinkler Co. and Star Sprinkler Inc. from 1995 to 2001. A listing of all the models covered under this voluntary replacement follows: AFFECTED MODELS CENTRAL "WET" SPRINKLERS (Manufactured from 1989 to 2000) GB GB4-FR GB-R1 BB2 ELOC ELO-GB QR GB-J GB4-EC GB-RS BB3 ESLO LD GB-1 GB4-QREC GB-R SD1 ELO SW-20 K17-231 GB-ALPHA GB-20 ROC SD2 ELO SW-24 Ultra K17 GB4 GB-20 QR BB1 17/32 SD3 ESLO-20 GB ELO-16 GB GB-QR GB-LO BB2 17/32 HIP ELO-231 GB GB MULTI-LEVEL GBR-2 LF BB3 17/32 WS ELO-GB GB-QR MULTI-LEVEL GB-EC GBR BB1 ELO-LH ELO-231 GBQR ELO-16 GB FR CENTRAL "DRY" SPRINKLERS (Manufactured rom Mid-1970s to 2001) A-1 GB GB4-EC ELO-16 GB H-1 GB-QR GB4-QREC ELO-16 GB FR J GB4 ELO-231 GB K GB4-FR ELO-GB QR GEM "WET" SPRINKLERS (Sold under Gem name from 1995 to 2001) F927 STAR "DRY" SPRINKLERS (Manufactured from 1996 to 1998) ME-1 SG SG-QR Q Q-QR. The fire sprinkler heads have the words "CENTRAL" or "STAR", the letters "CSC", the letter "G" in triangle, or a star-shaped symbol stamped on either the metal sprinkler frame or on the deflector. The model designation and date may also be stamped on the frame or deflector. The deflector is the flower, or gear-shaped metal piece at one end of the sprinkler head.
Hazard
These sprinkler heads can corrode or minerals, salts and other contaminants in water can affect the rubber O-ring seals. These factors could cause the sprinkler heads not to activate in a fire.
Injuries
Central has received 4 reports of "wet" sprinklers failing to activate during a fire and 9 similar reports on "dry" sprinklers. These incidents resulted in two property damage claims against Central.
Where it was sold
- The sprinklers were installed nationwide in a wide variety of buildings, including houses, apartments, hospitals, day care facilities, schools, dormitories, nursing homes, supermarkets, parking garages, warehouses, and office buildings.
Photos


Shopping for a replacement? Safer certified picks
If your item was recalled, these brands hold independent safety certifications and have no recall on record.
Avocado Green Mattress
Certified organic latex, wool, and cotton — no fiberglass.
Check pricePlushBeds
Natural latex, multiple whole-product certifications.
Check priceCertifications shown are editorial references — verify current status with the brand. Some links are affiliate links; we may earn a commission at no cost to you. See our disclosure.
Other fire / overheating recalls

Winco Fireworks International Recalls Unity 7 Shot 200 Gram Aerial Cake Fireworks Due to Risk of Serious Injury from Explosion and Burn Hazards
Winco Fireworks International

Winco Fireworks International Recalls Roman Candles 8 Shot Fireworks Due to Risk of Serious Injury from Explosion and Burn Hazards
Winco Fireworks International

Rowenta Recalls Cordless Vacuum Cleaners Due to Risk of Serious Injury from Fire and Burn Hazards
Rowenta

Cooper Lighting Recalls Metalux Optimized High Bay LED Light Fixtures Due to Fire Hazard
Cooper Lighting